What reverse power relay does?

The purpose of the reverse power relay is basically to prevent damage of the prime mover (turbine or motor) upon a reverse power condition.

Which relay will sense the reversal of power flow?

The reverse power relay senses any reverse direction of power flow and disconnects the generator to avoid any possible damage.

What is the difference between power relay and reverse power relay?

The directional relay will respond to any type of current, real or reactive. The reverse power relay, normally used in generator protection, responds to current drawn by a motor or generator (or resistor) that is producing work, as opposed to current that supports a magnetic field.

How do you reset reverse power?

Resetting the Reverse power relay In most of the manual modes, the reset is done by pressing a push button or by disconnecting the supply voltage for a short period of about one second.

What causes reverse power?

Insufficient energy flowing into the prime mover equals reverse power (amperes flowing INTO the generator instead of out). Amperes flowing into a generator causes the generator to become a motor which is keeping the generator–and its prime mover–spinning at a particular speed.

How do you check a reverse power relay?

How do you test reverse power trip? Reverse power trip can be tested by load shifting with the help of Governor control. when the Load has shifted sufficiently from the generator to be offloaded (Nearly 10% of the max rated ), reverse power relay will open the ACB of the same generator.

Which relay is used for reverse power protection of alternator?

The Reverse Power Relay T2000 will protect the generator from being run as an electric motor. The T2000 will protect the prime mover of the generator against physical damage, but will also protect the parallel running generators from overload caused by the inversed load shift in a reverse power situation.

What is TMS relay?

What is TMS or Time setting multiplier: The time setting multiplier is nothing but an adjusting or speeds up the tripping mechanism of the relay (it is called as the dial). The dial is nothing but a rotating disc, which rotates when the fault current in the relay coil reaches the pickup current.

What is standard setting of reverse power relay?

When a generator is operating in the motoring mode, the machine is consuming active power from the power system and if this active power crosses the set value, then after the set time delay the relay will operate to trip the Breaker. Normally reverse power setting is kept less than 50% of the motoring power.

What is the cause of reverse power?

How do you calculate reverse power relay?

In order to obtain this setting, the 25-100 watt relay should be selected. Consider now a single-phase system of 600 volts on which it is desired to detect a reverse power condition in excess of 20 KW. Assume a 100/5 CT and a 600/120 volt PT. = 20,000 = 200 secondary watts.

What is an inverse relay?

An inverse-time relay is one in which the operating time is approximately inversely proportional to the magnitude of the actuating quantity. The figure shows the time-current characteristics of an inverse current relay. At values of current less than the pickup, the relay never operates.

What is 50 and 50n relay?

50/51 and 50/51N relays. Overcurrent relays are the most commonly-used protective relay type. Time-overcurrent relays are available with various timing characteristics to coordinate with other protective devices and to protect specific equipment.

What is PSM and TSM in relay?

Time Setting Multiplier (TSM): The arrangement provided for setting the operating time of protective relay from zero sec to maximum permissible time for a specified current setting is known as time setting multiplier. Plug Setting Multiplier (PSM): It is the ratio of fault current in relay coil to pick-up current.

What is the difference between definite time relay & inverse time relay?

The IDMT relays operate as inverse time relay i.e., there exists an inverse relationship between time and current for lower values of fault current. While for higher values of fault current the relay acts as the definite time relay where the operating time is independent of fault current.