Paddle-type, also known as vane-type, flow switches are used in wet sprinkler systems to detect the flow of water and to send an alarm signal. To minimize false alarms due to pressure surges or air trapped in the sprinkler system, a mechanical delay is often used to postpone switch activation.

What is the purpose of a sprinkler system waterflow alarm?

NFPA 13, Standard for Installation of Sprinkler Systems, requires a local waterflow alarm on every sprinkler system with more than 20 sprinklers. The purpose of this waterflow alarm is not to provide occupants notification, but rather to provide outside building notification that the sprinkler system has been operated.

How does a vane switch work?

A vane operated flow switch is a device which utilizes the force exerted on a vane inserted in a flowing fluid to actuate an electric switch at a predetermined rate of flow. The electric switch may be used to start or stop pumps, open or close valves, actuate a warning lamp, sound an alarm, etc.

Are water motor gongs required?

As long as the sprinkler system flows water, the water motor gong will operate, which is a requirement of NFPA 13. Water flowing through the water motor gong is allowed to drain onto the ground.

Does a dry sprinkler system have a flow switch?

Note that dry systems must utilize pressure type flow switches. Per NFPA 13, paddle-type waterflow devices (C) are prohibited on dry pipe systems.

Are tamper switches normally open or closed?

NO is Normally Closed or NO is Normally Open Once the switch made by the third party is installed inside the waterflow, tamper, or pressure switch assembly, the lever or piston may normally push the button and quit pushing when there’s an alarm or supervisory.

What is supervisory pressure?

Air pressure switches initiate a supervisory signal if the air pressure in the dry pipe valve dips or rises from normal. This allows the authorized building personnel to take action to prevent false activation of the sprinkler system or prevent damage to the system.

What is the use of jockey pump in fire fighting system?

A jockey pump is a small pump connected to a fire sprinkler system to maintain pressure in the sprinkler pipes. This is to ensure that if a fire-sprinkler is activated, there will be a pressure drop, which will be sensed by the fire pumps automatic controller, which will cause the fire pump to start.

Where do you put a flow switch?

The flow switch should be located in a horizontal section of pipe where there is a straight horizontal run of at least 5 pipe diameters on each side of the flo w switch. The flow switch may be installed in a vertical pipe if the flow is in the upward direction.

Can water flow alarms be silenced?

The exterior audible device shall sound upon water flow switch activation only and shall not be silenced until the water flow switch has been reset.

What is the difference between a flow switch and a pressure switch?

One visible difference between pressure switches and paddle flow switches is the lack of a paddle in the latter. Pressure switches have no parts that reach the open pipe. It’s this distinction that makes these devices safe for dry-pipe, preaction, and deluge fire sprinkler systems that surge a lot of water pressure.